Display screen
System message
Possible cause
Measures to rectify the fault
A01
Enclosure door open
Door open or door limit switch incor- rectly positioned
Close door, position door limit switch cor- rectly, check connection if necessary
A02
Internal temperature of enclosure too high
Cooling capacity inadequate/unit un- dersized Error as a consequence of messages A03 to A17.
Check cooling capacity
A03
Filter monitoring
Filter mat soiled
Clean or replace;
reset the e-Comfort controller
A04
Ambient temperature too high/low
Ambient temperature outside permissi- ble operating range (+10°C to +60°C)
Raise or lower the ambient temperature (e.g. heat or ventilate the room)
A05
Icing hazard
Operational display in case of icing haz- ard.
Evaporator coil fan may be mechani- cally blocked, defective, or cold air out- let obstructed.
Set the enclosure interior temperature to a higher value. Check the evaporator fan; release or exchange if necessary.

Display screen
System message
Possible cause
Measures to rectify the fault
A06
PSAH pressure switch
Ambient temperature too high
Lower the ambient temperature; reset the e-Comfort controller
Condenser soiled
Clean the condenser;
reset the e-Comfort controller
Filter mat soiled
Clean or replace;
reset the e-Comfort controller
Condenser fan defective
Replace;
reset the e-Comfort controller
E-valve defective
Repair by refrigeration engineer; reset the e-Comfort controller
PSAH pressure switch defective
Refrigeration engineer to exchange reset the e-Comfort controller
A07
Evaporator coil
Lack of refrigerant; sensor in front of or behind condenser defective
Repair by refrigeration engineer; reset the e-Comfort controller
A08
Condensate warning
Condensate discharge kinked or blocked
Check condensate drainage;
correct any kinks or blockages in the hose
Only for units with optional condensate evaporation
Check the evaporation unit, replace if neces- sary
A09
Condenser fan
Blocked or defective
Clear the blockage; replace if necessary
A10
Evaporator fan
Blocked or defective
Clear the blockage; replace if necessary
A11
Compressor
Compressor overloaded (internal wind- ing protection)
No action required;
Unit switches on again independently
Defective (check by measuring the winding resistance)
Replace by a refrigeration engineer
A12
Condenser tempera- ture sensor
Open or short-circuit
Replace
A13
Ambient temperature sensor
Open or short-circuit
Replace
A14
Icing temperature sen- sor
Open or short-circuit
Replace
A15
Condensate warning temperature sensor
Open or short-circuit
Replace
A16
Internal temperature sensor
Open or short-circuit
Replace
A17
Phase monitoring
For three-phase devices only: Incorrect rotary field/phase absent
Swap two phases
A18
EPROM error
New board installed incorrectly
Software update needed (only following board installation with more recent soft- ware): Enter the programming level with Code 22;
press button 1 and confirm with "Set" until "Acc" appears. Next, disconnect the unit from the mains and reconnect.
A19
LAN/Master-Slave
Master and slave not connected
Check setting and/or cable